Senseca Germany GmbH

ECO 210-3 - Fine manometer (formerly G 1107)

Producer

Characteristics
The primary focus in the development of the new ECO-line was placed on the essential functions of the measurement technology.
The heart of the instrument – the sensor – is a high-class component – which excels in this instrument class.
The high reliability, speed and precision of the ECO-line variants, packed in a compact an water protected housing makes the instruments an ideal partner of industry and craft sector, Made in Germany.
ECO 210 Series – The reference class in pocketsize.

ECO 210-3
Fine pressure manometer for application in Heating / Ventilation / Air-conditioning (HVAC)
The measurement range up to 200 hPa (mbar) / 20 kPa and the high resolution up to 0.1 Pascal in the optimized fine pressure mode covers the main applications for gas pressure 150 hPa (mbar) and burner adjustments with a single instrument.
The high precision simplifies e.g. adjustments of dynamic pressure or draft measurements.
The measurement is independent of the instruments orientation – better than many, even much more expensive, competitors.

Measurement rate:
Slow: 2.5 measurements per second
Fast: 25 measurements per secon
Power supply:
2 x AA battery (included in the scope of delivery)
Power consumption:
ca. 1 mA (slow measurement SLO), battery life ca. 3000 h
Weight:
150 g incl. battery
Housing material:
Break-proof ABS housing
Measuring range:
choice from -2000..+2000 Pa to -200.0..+200.0 hPa (mbar)
(FINE: -200.0..+200.0 Pa)
Connections:
2 tube connections, interchangeable with G1/8 universal ports
Operating conditions:
-20 to +50 °C; 0 to 95 % r.h. (temporarily 100 % r.h.)
Storage temperature:
-20...70 °C
Protection type:
IP 67 (pressure connections must be protected from soiling and moisture)
Measurements:
Difference
Display:
3-line segment LCD, additional symbols, illuminated (white, illumination time adjustable),
overhead display on key press
Dimensions:
108 x 54 x 8 mm without pressure connection
Additional functions:
NULL / Tare function
FINE: With 0.1 Pa resolution
AVR: Averaging over 2 s / 5 s / 10 s
Standard functions:
Min/Max/Hold, Auto-Power-Off-function / if activated, the product switches off automatically
Display units:
Pa, hPa, mbar, PSI, mmHg (Torr)
Precision typ. @ 25 °C:
+/- 0.1 % FSS
Precision max. (-20 ... 50 °C):
+/- 1 % FSS
Max. overload:
+/- 1700 hPa
Adjustment:
Zero point and slope
 
 
Enquire for more information
please weait… Your data is being loaded...

Article no. Measuring range Working temperature Set-Option Current supply minimal quantity Quantity
PCE
486718 ECO 210-3-UT - Fine manometer (formerly G 1107) -200.0 ... +200.0 hPa -2000 ... +2000 Pa, -20.00 ... +20.00 hPa) -20 ... +50 °C Device only 2 x AA batteries 1 Delivery time
486960 ECO 210-3-QC6 - Fine manometer (formerly G 1107) -200.0 ... +200.0 hPa -2000 ... +2000 Pa, -20.00 ... +20.00 hPa) -20 ... +50 °C Device only 2 x AA batteries 1 Delivery time
486961 ECO 210-3-MCM - Fine manometer (formerly G 1107) -200.0 ... +200.0 hPa -2000 ... +2000 Pa, -20.00 ... +20.00 hPa) -20 ... +50 °C Device only 2 x AA batteries 1 Delivery time
486962 ECO 210-3-ST6 - Fine manometer (formerly G 1107) -200.0 ... +200.0 hPa -2000 ... +2000 Pa, -20.00 ... +20.00 hPa) -20 ... +50 °C Device only 2 x AA batteries 1 Delivery time
487003 ECO 210-3-MCM - Fine manometer (formerly G 1107) -200.0 ... +200.0 hPa -2000 ... +2000 Pa, -20.00 ... +20.00 hPa) -20 ... +50 °C Device incl. 1 m tube 6x1 PVC, case GKK 1002, 2 quick connect sockets GDZ-MCF 2 x AA batteries 1 Delivery time
487005 ECO 210-3-QC6 - Fine manometer (formerly G 1107) -200.0 ... +200.0 hPa -2000 ... +2000 Pa, -20.00 ... +20.00 hPa) -20 ... +50 °C Device incl. 1 m tube 6x1 PVC, case GKK 1002 2 x AA batteries 1 Delivery time
487006 ECO 210-3-ST6 - Fine manometer (formerly G 1107) -200.0 ... +200.0 hPa -2000 ... +2000 Pa, -20.00 ... +20.00 hPa) -20 ... +50 °C Device incl. 1 m tube 6x1 PVC, case GKK 1002 2 x AA batteries 1 Delivery time
487007 ECO 210-3-UT - Fine manometer (formerly G 1107) -200.0 ... +200.0 hPa -2000 ... +2000 Pa, -20.00 ... +20.00 hPa) -20 ... +50 °C Device incl. 1 m tube 6x1 PVC, case GKK 1002 2 x AA batteries 1 Delivery time
487010 ECO 210-3-UT - Fine manometer (formerly G 1107) -200.0 ... +200.0 hPa -2000 ... +2000 Pa, -20.00 ... +20.00 hPa) -20 ... +50 °C Measuring device, incl. 1 m rubber tube 8 mm, suitcase GKK 1002 2 x AA batteries 1 Delivery time
487011 ECO 210-3-UT-WPD - Fine manometer (formerly G 1107) -200.0 ... +200.0 hPa -2000 ... +2000 Pa, -20.00 ... +20.00 hPa) -20 ... +50 °C Device, incl. 1 m tube 6x1 PVC, case GKK 1002, factory calibration WPD5, not DAkkS accredited 2 x AA batteries 1 Delivery time